OUTGASSING
TEST RESULTS
|
| Pacific
Panels unique vacuum process eliminates volatile organic materials
from the honeycomb panels. Test samples are placed in a sealed vial
and heated to 100 degrees C for 30 minutes. The headspace above the
sample is then analyzed by Gas Chromatography / Mass Spectrometry
to determine the presence of any organic out gassing materials. |
|
Sample
|
Total
Organics Detected
(ppm in headspace)
|
Organic Compounds in Sample
|
|
Honeycomb
Core
|
<0.01
|
NONE
|
|
Adhesive
|
<0.01
|
NONE
|
|
|
FLAME
SPREAD CLASSIFICATION AND SMOKE DENSITY DEVELOPED
|
| Pacific
Panels Aluminum Cleanroom Wall Panels were tested in accordance with
ASTM Designation E84-97a, "Standard Method of Test for Surface
Burning Characteristics of Building Materials". This test procedure
is comparable to UL 723, ANSI /NFPA No. 225, and UBC No. 8-1. |
|
Test
Results
|
SAMPLE
IDENTIFICATION
|
FLAME SPREAD
|
SMOKE DENSITY
|
|
Honeycomb
Panel
|
5
|
5
|
|
|
FLAME
SPREAD CLASSIFICATION
|
|
SAMPLE IDENTIFICATION
|
UBC CLASSIFICATION`
|
NFPA CLASS
|
|
Honeycomb
Panel
|
1
|
A
|
|